Fire shutter Fire 5000 Type RGC EI2 60

Fire shutter Fire 5000 is an excellent fire protection for closing or dividing larger spaces. Partly thanks to its high fire resistance of 60 minutes (in accordance with EI (1) and EW criteria). Based on two-sided testing according to the European standard EN 1634-1, this door is highly suitable for situations where high fire resistance is required and in situations where environmentally hazardous substances are stored, so-called PGS areas.

Classified according to EN 13501-2 at EI (1) 60 and EW 60 minutes.
CE marked in accordance with EN 13241 and also EN 16034.

Select fire class

 

EW60

Maximum size: 8000x 9250 mm.
Area: 40 m2


Tested on both sides in accordance with EN 1634-1.
 
Classified according to EN 13501-2 in EW 60 minutes.
 
Composite slats classified according to EN 13501-1 for fire class B-s1, d0.
 
Validated cycle test in accordance with C2 (10,000 movements); C3 pending (50,000 movements).
 
CE marked in accordance with EN 13241 and also EN 16034.

EI2 60

Maximum size: 8000x 9250 mm.
Area: 40 m2


Tested on both sides in accordance with EN 1634-1.
 
Classified according to EN 13501-2 at EI (1) 60 minutes.
 
Composite slats classified according to EN 13501-1 for fire class B-s1, d0.
 
Validated cycle test in accordance with C2 (10,000 movements); C3 pending (50,000 movements).
 
CE marked in accordance with EN 13241 and also EN 16034.

Suitable for frequent use

Fire shutter Fire 5000 is suitable for fire protection of frequently used enclosures both indoors and outdoors.

Installation only possible on wall. Mounting surfaces: aerated concrete, aerated concrete, sand-lime brick, concrete, masonry, fire-resistant prepared steel construction, reinforced metal stud through integrated construction

 

Standard delivered with failsafe

Gravity failsafe 400 V chain wheel drive incl. control box with integrated battery optical/acoustic signaling.

Door leaf constructed of galvanized steel leaves (front) and fire-resistant composite leaves (rear) with a mixed white texture

Fire shutter Requires annual statutory inspection

We recommend purchasing a tailor-made service agreement to ensure that the annual statutory inspection, operation and maintenance is carried out. 

Technical specifications

At Alux, we believe that a good collaboration leads to a good solution. We are always ready to advise you throughout your project or help you if you have any questions about our solutions.

Contact our service team at alux@alux.dk for non-binding advice and quotes.

 
 
 
 

Downloads


  • The 400V motors are equipped with a 24V emergency motor. In normal use, the blind opens and closes with the 400V motor and the emergency motor (dead man's function).

    In an emergency, the emergency motor will close the blind automatically with power from the batteries in the control panel. The fire blind should only be used indoors and should be run a maximum of 5 times a day.

    We recommend an annual inspection or after 500 runs and a monthly test of the emergency system. Batteries should be changed every two years.

  • 63 x 36 mm profiles consisting of a synthetic material bonded to an inner core of high performance insulation material.

  • Width: 6,000 mm.

    Height: 5,000 mm.

    Area: 22 m2

  • 123 x 72 mm galvanized steel with fire expanding material.

  • 37 kg/m2

  • Supplied without guide rail and roller covers.

    A cover box can be purchased at an additional cost.

  • Guide rails, brackets etc. are supplied galvanized.

    The mat is available in light gray.

  • 400V geared motor mounted in optional side. In the event of a power failure, an additional 24V DC motor ensures that the fire shutter closes.

  • ABA or ABDL system. Daily operation with key switch or code switch.

  • Blinds are always installed as surface-mounted blinds. It is assumed that there is a solid and suitable building component as a fastening base from the reveal and 220 mm in on both sides and throughout the entire height of the blind.

  • - Annual statutory inspection by a service company.

    - Functional testing of engine, steering and safety equipment.

    - Check suspension, fasteners and slats for damage.

    - Tightening of moving parts.

    - Clean guide rails and, if necessary, lubricate bearings and sliding brackets.

  • We recommend purchasing a tailor-made service agreement to ensure that the annual statutory inspection, operation and maintenance is carried out.

Related products

 
 

Fire shutter Fire 5000 Type RGC EI2 60 

This Fire 5000 Fire shutter is an excellent solution for fire-resistant closure or partitioning of rooms. Partly thanks to its high fire resistance of 60 minutes, this Fire shutter is extremely suitable for situations where high fire resistance is required. 

Fire shutter Fire 5000 Type RGC EI2 60

Fire shutter Fire 4000 Type RGS EW 60, EW 90 & EW120

This Fire 4000 Fire shutter is an excellent solution for fireproof closing or dividing rooms. This Fire shutter is highly suitable for everyday use and situations where low to medium fire resistance is required.

Fire shutter Fire 4000 Type RGS EW 60, EW 90 & EW120

Fire Curtain Fire 5000 Type RGT EI2 60 & EI2 120

A heat-insulating fire protection that reduces heat radiation to a minimum. The temperature on the surface of the fire curtain can be kept lower than 140° for a minimum of 30 minutes. The compact and solid design of the fire curtain can be easily integrated into both ceilings and frames.

Fire Curtain Fire 5000 Type RGT EI2 60 & EI2 120